Skip to content
Home > Series > 3Phase > ADT

ADT Series

High Performance 3-Phase RFI Power Line Filters for Delta Applications


UL Recognized

Catalog Data Sheet
Printer friendly version

 

ADT Series

  • Designed for very high insertion loss for Delta three phase, three wire applications
  • Available with common or differential mode coils

Ordering Information

Available Part Numbers

Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.

63ADT6 63ADT6S
100ADT6 100ADT6S
160ADT6 160ADT6S
200ADT6 200ADT6S

 

 

Specifications

Maximum leakage current, each Line to Ground @ 277VAC 60 Hz:
  ADT6 1.3 A
  63ADT6S 2.6 A
  100, 160, 200ADT6S 4.6 A
     
Hipot rating (one minute):
  Line to Ground 2210 VDC
  Line to Line 2158 VDC
     
Operating Frequency: 50 / 60 Hz
     
Rated voltage (max.):  
  Phase to Phase 480 VAC
  Phase to Ground 277 VAC
     
Rated Current: 63A to 200A
   
Operating Ambient Temperature Range (at rated current Ir):
  -10°C to +40°C
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io = Ir √(85-Ta)/45

Electrical Schematics

63ADT6

100, 160 & 200 ADT6

 

ADT6S

Case Styles

Typical Dimensions:  
  63ADT6, 63ADT6S & 100 ADT6S Terminals (6): 3/8 - 16
Torque 70 lbf-in. [7.91 N-m] max.
  100ADT6, 160 & 200 ADT6/S Terminals (6): 7/16-20
Torque 125 lbf-in. [14.12 N-m] max.

 

Case Dimensions

Part No. A B C D E F G H J K
(max.) (max.) (max.) ± .030 (max.) ±.030 ± .030 ± .030 ± .030 (max.)
± .76 ± .76 ± .76 ± .76 ± .76
63ADT6 14.00 10.00 3.50 8.50 10.00 11.97 7.50 1.75 2.00 6.00
355.6 254.0 89.0 216.0 254.0 304.0 190.5 44.4 50.8 152.4

63DT6S 19.00 10.00 4.50 8.50 15.00 16.97 7.50 3.00 3.00 6.00
482.6 254.0 114.3 216.0 381.0 431.0 190.5 76.2 76.2 152.4

100ADT6 19.00 10.00 4.50 8.50 15.00 16.97 7.5 3.00 3.00 6.00
482.6 254.0 114.3 216.0 381.0 431.0 190.5 76.2 76.2 152.4

100ADT6S 19.00 11.00 4.50 8.50 15.00 16.97 8.50 3.00 3.00 6.00
482.6 279.4 114.3 216.0 381.0 431.0 215.9 76.2 76.2 152.4

160/200ADT6 19.00 10.00 4.50 8.50 15.00 16.97 7.50 3.00 3.00 6.00
482.6 254.0 114.3 216.0 381.0 431.0 190.5 76.2 76.2 152.4

160/200ADT6S 22.00 13.00 4.50 11.50 18.00 19.97 10.50 2.75 3.00 7.00
558.8 330.2 114.3 292.2 457.2 507.2 266.7 69.8 76.2 177.8

 

Performance Data

Typical Insertion Loss
Measured in closed 50 ohm system
 

63ADT6

63ADT6S

100ADT6

100ADT6S

160ADT6

160ADT6S

200ADT6

200ADT6S

Minimum Insertion Loss in dB:
Measured in closed 50 ohm system
     
Common Mode / Asymmetrical (Line to Ground)   Differential Mode / Symmetrical (Line to Line)

 
Current Rating Frequency - MHz
.01 .1 1 10 30 100 300

63ADT6 45 85 95 100 100 100 100
100ADT6 45 85 90 100 100 100 100
160ADT6 45 80 90 100 100 100 100
200ADT6 45 77 88 100 100 100 100
63ADT6S 28 45 90 90 90 90 90
100ADT6S 38 60 95 100 100 100 100
160ADT6S 37 58 85 100 100 100 100
200ADT6S 35 54 80 100 100 100 100

 
Current Rating Frequency - MHz
.01 .1 1 10 30 100 300

63ADT6 35 100 100 100 100 100 100
100ADT6 43 100 100 100 100 100 100
160ADT6 44 100 100 100 100 100 100
200ADT6 43 100 100 100 100 100 100
63ADT6S 35 100 100 100 100 100 100
100ADT6S 43 100 100 100 100 100 100
160ADT6S 44 100 100 100 100 100 100
200ADT6S 43 100 100 100 100 100 100

 

USA Customer Service: 1-800-468-2023
Corcom Products Direct: 1-847-680-7400
Germany: 49-89-6089-0
  Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.