Skip to content
Home > Series > 3Phase > AYA

AYA Series

3-Phase WYE RFI Power Line Filters


UL Recognized*

* Does not include 16AYA10, 36AYA10, 63AYA10 and 100AYA6A

Catalog Data Sheet
Printer friendly version

 

AYA Series

  • For 3-phase, four wire, WYE  applications
  • Cost-effective, universal 3-phase filters
  • Good attenuation over the complete frequency range of 10kHz to 30MHz
  • Two different mounting styles available

Ordering Information

Available Part Numbers

Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.

Flange Mount Bulkhead Mount
16AYA6A 16AYA6
16AYA10 25AYA6
25AYA6A 36AYA6
36AYA6A 50AYA6
36AYA10  
50AYA6A  
63AYA6A  
63AYA10  
100AYA6A  

 

 

Specifications

Maximum leakage current, each Line to Ground:
  @ 120 VAC 60 Hz 1.62mA
  @ 250 VAC 50 Hz 2.82mA
     
Hipot rating (one minute):
  Line to Ground 1500 VAC
  Line to Line 1450 VDC
     
Operating Frequency: 50 / 60 Hz
     
Rated voltage (max.):  
  Phase to Phase 440 VAC
  Phase to Ground 250 VAC
     
Rated Current: 16A to 50A
   
Operating Ambient Temperature Range (at rated current Ir):
  -10°C to +40°C
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io = Ir √(85-Ta)/45

Electrical Schematic

 

Case Styles

AYA6A (Flange mount with screw terminals)

Typical Dimensions:  
  Mounting Slots (4): ..425 x .254 [10.8 x 6.6]
  16 & 25A Terminals (8): 8-32
Torque 26 lbf-in. [2.94 N-m] max.
  36A Terminals (8): 10-32
Torque 27 lbf-in. [3.05 N-m] max.
  50, 63 & 100A Terminals (8): 1/4-20
Torque 56 lbf-in. [6.33 N-m] max.

AYA6 (Bulkhead mount with screw terminals)

Typical Dimensions:  
  Mounting Holes (4): M5 x 8
  16 & 25A Terminals (8): 8-32
Torque 26 lbf-in. [2.94 N-m] max.
  36A Terminals (8): 10-32
Torque 27 lbf-in. [3.05 N-m] max.
  50A Terminals (8): 1/4-20
Torque 56 lbf-in. [6.33 N-m] max.

16AYA10

Typical Dimensions:  
  Mounting Slots (4): ..425 x .254 [10.8 x 6.6]
  Terminal blocks (8): 4mm²
Torque 7.08 lbf-in. [0.8 N-m] max.
  Ground terminal (1): M5
Torque 26.58 lbf-in. [3.0 N-m] max.

 

 

36AYA10

Typical Dimensions:  
  Mounting Slots (4): ..425 x .254 [10.8 x 6.6]
  Terminal blocks (8): 10mm²
Torque 15.93 lbf-in. [1.8 N-m] max.
  Ground terminal (1): M5
Torque 26.58 lbf-in. [3.0 N-m] max.

63AYA10

Typical Dimensions:  
  Mounting Slots (4): ..425 x .254 [10.8 x 6.6]
  Terminal blocks (8): 16mm²
Torque 20.35 lbf-in. [2.3 N-m] max.
  Ground terminal (1): M6
Torque 53.1 lbf-in. [6.0 N-m] max.

Case Dimensions

Part No. A B C D E*
(max.) (max.) (max.) (max.) (max.)
16AYA6 / A
25AYA6 / A
7.91 4.37 1.97 5.94 5.51
201.0 111.0 50.0 151.0 140.0

36AYA6 / A
50AYA6 / A
7.91 4.37 2.56 5.94 5.51
201.0 111.0 65.0 151.0 140.0

63AYA6 / A
100AYA6A
7.91 4.37 2.56 5.94 5.51
201.0 111.0 50.0 151.0 140.0

16AYA10 6.97 4.37 1.97 5.94 5.51
177.0 111.0 50.0 151.0 140.0

36AYA10 7.88 4.37 2.56 5.94 5.51
200.0 111.0 65.0 151.0 140.0

63AYA10 10.98 5.08 2.52 8.43 6.26
279.0 129.0 64.0 214.0 159.0

* Does not apply to bulkhead models

 

Performance Data

Typical Insertion Loss
Measured in closed 50 ohm system
 

16AYA

25AYA

36AYA

50AYA

63AYA

100AYA

 

 

Minimum Insertion Loss in dB:
Measured in closed 50 ohm system
     
Common Mode / Asymmetrical (Line to Ground)   Differential Mode / Symmetrical (Line to Line)

 
Current Rating Frequency - MHz
.01 .05 .1 .5 1 5 10 30

16A 2 11 19 52 53 70 61 30
25A 2 12 19 46 49 64 54 27
36A 1 10 18 49 54 63 57 32
50A 1 8 14 43 47 63 53 29
63A 2 10 22 50 60 75 70 55
100A 1 15 22 55 60 65 55 50

 
Current Rating Frequency - MHz
.01 .05 .1 .5 1 5 10 30

16A 14 31 30 82 87 76 77 47
25A 20 36 38 85 81 68 69 33
36A 20 39 36 86 78 65 62 35
50A 20 30 38 85 82 67 66 38
63A 30 40 45 90 85 70 70 60
100A 20 35 45 80 80 65 60 55

 

 

USA Customer Service: 1-800-468-2023
Corcom Products Direct: 1-847-680-7400
Germany: 49-89-6089-0
  Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.