| Single Phase External Power Line Filter for Frequency Converters |

UL Recognized
Catalog Data Sheet
Printer friendly version
|
|
 |
FC Series
- Designed for frequency inverters and variable speed motor drives
- Suitable for electronically noisy environments
- Protects programmable logic controllers from RF noise on the AC power line
- Side flanges for easy mounting
- Touch safe terminals provide easy connections and prevent inadvertent contact for safety in the most demanding applications
Ordering Information

Available Part Numbers
Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.
|
|
Specifications
| Maximum leakage current, each Line to Ground: |
| |
|
B suffix |
no suffix |
| |
@ 120 VAC 60 Hz |
3.9 mA |
3.8 mA |
| |
@ 250 VAC 50 Hz |
7.0 mA |
6.7 mA |
| |
|
|
| Hipot rating (one minute): |
| |
Line to Ground |
2250 VDC |
| |
Line to Line |
1450 VDC |
| |
|
|
| Operating Frequency: |
50 / 60 Hz |
| |
|
|
| Rated voltage (max.): |
250 VAC |
| |
|
|
| Rated Current: |
6A to 50A * |
| |
* refer to part number for rating |
| Operating Ambient Temperature Range (at rated current Ir): |
| |
|
-10°C to +40°C |
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io = Ir √(85-Ta)/45
|
Electrical Schematics
FC10

FC10B

|
Case Styles
6, 12, 16FC10
| Typical Dimensions: |
|
| |
Line/Load Terminals (4): |
DIN type accepts 10AWG solid / 12AWG stranded |
| |
Ground Terminals (2): |
8-32
Torque 18 lbf-in. [2.03 N-m] max. ±2[..22] |
| |
Mounting Holes (4): |
.203 x .156 [5.16 x 3.96] |
25, 36FC10

| Typical Dimensions: |
|
| |
Line/Load Terminals (4): |
DIN type accepts 8AWG solid / 10AWG stranded |
| |
Ground Terminals (2): |
8-32
Torque 18 lbf-in. [2.03 N-m] max. ±2[..22] |
| |
Mounting Slots (4): |
.260 [6.6] wide |
|
|
Case Dimensions
| Part No. |
A |
B |
C |
D |
E |
F |
| (max.) |
(max.) |
(max.) |
± .020 |
(max.) |
± .010 |
| ± .51 |
± .254 |
| 6FC10 |
4.60 |
3.10 |
1.78 |
2.677 |
3.70 |
2.00 |
| 116.8 |
78.7 |
45.21 |
67.8 |
94.0 |
50.8 |
|
12FC10/10B
16FC10/10B |
5.47 |
3.96 |
2.18 |
3.50 |
4.53 |
2.00 |
| 139.0 |
100.6 |
55.4 |
88.9 |
114.8 |
50.8 |
|
25, 36, 50
FC10/FC10B |
6.90 |
5.48 |
2.55 |
4.90 |
5.94 |
2.756 |
| 175.3 |
139.2 |
64.77 |
124.5 |
150.9 |
70.0 |
|
|
Performance Data
| Typical Insertion Loss |
| Measured in closed 50 ohm system |
| |
6FC10

|
12FC10

|
16FC10

|
25FC10

|
36, 50FC10

|
12, 16FC10B

|
25FC10B

|
36FC10B

|
50FC10B

|
 |
| Minimum Insertion Loss in dB: |
| Measured in closed 50 ohm system |
| |
|
|
| Common Mode / Asymmetrical (Line to Ground) |
|
Differential Mode / Symmetrical (Line to Line) |
|
|
|
| Part No. |
Frequency - MHz |
| .01 |
.03 |
.05 |
.1 |
.5 |
1 |
5 |
10 |
30 |
|
| 6FC10 |
9 |
19 |
26 |
37 |
65 |
65 |
50 |
40 |
35 |
| 12FC10 |
5 |
17 |
25 |
37 |
65 |
65 |
65 |
60 |
35 |
| 16FC10 |
4 |
15 |
22 |
36 |
65 |
65 |
70 |
70 |
35 |
| 25FC10 |
2 |
14 |
22 |
36 |
75 |
75 |
70 |
70 |
48 |
| 36, 50FC10 |
- |
6 |
14 |
27 |
68 |
75 |
70 |
70 |
50 |
| 12, 16FC10B |
16 |
28 |
37 |
50 |
81 |
76 |
63 |
55 |
38 |
| 25FC10B |
14 |
25 |
36 |
49 |
91 |
88 |
71 |
64 |
46 |
| 36FC10B |
11 |
25 |
37 |
50 |
81 |
87 |
73 |
66 |
49 |
| 50FC10B |
11 |
24 |
36 |
49 |
81 |
75 |
62 |
54 |
37 |
|
|
|
| Part No. |
Frequency - MHz |
| .01 |
.03 |
.05 |
.1 |
.5 |
1 |
5 |
10 |
30 |
|
| 6FC10 |
10 |
10 |
35 |
60 |
75 |
75 |
60 |
50 |
45 |
| 12FC10 |
14 |
14 |
30 |
51 |
75 |
75 |
75 |
70 |
45 |
| 16FC10 |
14 |
14 |
29 |
55 |
75 |
75 |
75 |
70 |
45 |
| 25FC10 |
14 |
14 |
17 |
42 |
75 |
75 |
70 |
70 |
50 |
| 36, 50FC10 |
14 |
14 |
17 |
42 |
75 |
75 |
70 |
70 |
50 |
| 12, 16FC10B |
30 |
32 |
46 |
64 |
91 |
86 |
77 |
78 |
65 |
| 25FC10B |
24 |
24 |
31 |
46 |
92 |
87 |
86 |
75 |
55 |
| 36FC10B |
27 |
33 |
27 |
41 |
89 |
88 |
82 |
74 |
55 |
| 50FC10B |
30 |
32 |
48 |
64 |
91 |
87 |
82 |
79 |
67 |
|
|
|
| USA Customer Service: |
1-800-468-2023 |
| Corcom Products Direct: |
1-847-680-7400 |
| Germany: |
49-89-6089-0 |
|
|
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. |