Skip to content
Home > Series > Power Line > SK

SK Series

High Performance K Series RFI Line Filters for SMPS Emission Control


UL Recognized
CSA Certified
VDE Approved

Catalog Data Sheet
Printer friendly version

 

SK Series

  • Designed to reduce conducted noise to acceptable limits for equipment that must comply with FCC / EN specifications
  • Utilizes significantly higher element values than the general purpose K Series which makes them better suited for equipment with Line to Ground and Line to Line conducted emissions including those with switching power supplies
  • ESK6C and VSK6C incorporate separate ground circuit inductor to isolate the equipment chassis from power line ground at RF frequencies

Ordering Information

*1-15A: IEC 60320-1 C14 inlet mates with C13 connector

Available Part Numbers

Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.

3VSK1 3ESK1
3VSK3 3ESK3
3VSK7 3ESK7
3VSK7M 3ESK7M
6VSK1 6ESK1
6VSK3 6ESK3
6VSK7 6ESK7
6VSK7M 6ESK7M
10VSK1 10ESK1
10VSK3 10ESK3
10VSK7 10ESK7
10VSK7M 10ESK7M
20VSK6 20ESK6
30VSK6 30ESK6
30VSK6C 30ESK6C
40VSK6  

 

 

Specifications

Maximum leakage current, each Line to Ground:
    VSK Models ESK Models
  3, 6 & 10 Amps    
  @ 120 VAC 60 Hz .4mA .21mA
  @ 250 VAC 50 Hz .7 mA .36 mA
       
  20, 30 & 40 Amps    
  @ 120 VAC 60 Hz .75 mA .3 mA
  @ 250 VAC 50 Hz 1.25 mA .5 mA
     
Hipot rating (one minute):
  Line to Ground 2250 VDC
  Line to Line 1450 VDC
     
Operating Frequency: 50 / 60 Hz
     
Rated voltage (max.): 250 VAC
     
Rated Current: 3A to 40A
   
Operating Ambient Temperature Range (at rated current Ir):
    -10°C to +40°C
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io = Ir √(85-Ta)/45

Electrical Schematic

Accessories

GA400: NEMA 5-15P to IEC 60320-1 C13 line cord

 

Case Styles

SK1

Typical Dimensions:
  Line/Load Terminals(4): .250 [6.3] with .07 [1.8] Dia. hole
  Ground Terminal(1): .250 [6.3] with .07 x .16 [1.8 x 3.8] slot
  Mounting Holes (2): .188 [4.75] Dia.

SK3 (3A)

Typical Dimensions:  
  Wire leads (5): .4.0 [101.6] Min. AWG18
  Mounting Holes (2): .188 [4.75] Dia.

SK3 (6A)

Typical Dimensions:  
  Wire leads (5): .4.0 [101.6] Min. AWG18 (AWG16 for 10A)
  Mounting Holes (2): .188 [4.75] Dia.

 

SK6 (20A)

Typical Dimensions:  
  Terminals (5): 8-32
Torque 18 lbf-in. [2.03 N-m] max. ±2[.22]
  Mounting Holes (2): .188 [4.75] Dia.

SK6 (30A)

Typical Dimensions:  
  Terminals (5): 10-32
Torque 27 lbf-in. [3.05 N-m] max. ±2[.22]
  Mounting Slots (4): .250 x .156 [6.35 x 3.96] Dia.

SK6C (30A)

Typical Dimensions:  
  Terminals (5): 10-32
Torque 27 lbf-in. [3.05 N-m] max. ±2[.22]
  Mounting Slots (4): .250 x .156 [6.35 x 3.96] Dia.

 

 

 

SK6 (40A)

Typical Dimensions:  
  Terminals (5): 10-32
Torque 27 lbf-in. [3.05 N-m] max. ±2[.22]
  Mounting Slots (4): .156 x .203 [3.96 x 5.15] Dia.

SK7 & SK7M (metric inserts)

Typical Dimensions:
  Load Terminals(2): .250 [6.3] with .07 [1.8] Dia. hole
  Ground Terminal(1): .250 [6.3] with .07 x .16 [1.8 x 3.8] slot
  Line Inlet (1): IEC 60320-1 C14
  K7 Inserts (2): 6-32 x 1/4
  K7M Inserts (2): M3x.5

Recommended Panel Cutouts


tolerance ± .005 [0.13]
Back mount only

Case Dimensions

Part No. A B C D E
(max.) (max.) (max.) ± .015** (max.)
± .38
3VSK1, 3ESK1 3.85 2.07 1.16 2.938 3.35
97.8 52.6 29.5 74.63 85.1

3VSK3, 3ESK3 2.56 2.07 1.16 2.938 3.35
65.0 52.6 29.5 74.63 85.1

3VSK7, 3VSK7M,
3ESK7, 3ESK7M
3.21 2.25 1.53 1.575 .063*
81.5 57.2 38.9 40.01 16.0*

6VSK1, 6ESK1 4.34 2.25 1.28 3.427 3.83
110.2 57.2 32.5 87.05 97.3

6VSK3, 6ESK3

3.05 2.25 1.28 3.427 3.83
77.5 57.2 32.5 87.05 97.3

6VSK7, 6VSK7M,
6ESK7, 6ESK7M
3.21 2.25 1.78 1.575 0.63*
81.5 57.2 45.2 40.01 16.0*

10VSK1, 10ESK1 4.97 2.25 1.78 4.063 4.46
126.2 57.2 45.2 103.2 113.3

10VSK3, 10ESK3 3.69 2.25 1.78 4.063 4.46
93.7 57.2 45.2 103.2 113.3

10VSK7, 10ESK7M,
10ESK7, 10ESK7M
4.34 2.25 1.78 1.575 0.63*
110.0 57.2 45.2 40.01 16.0*

20ESK6, 20VSK6 5.09 2.25 1.78 4.063 4.46
127.3 57.2 45.2 103.2 129.3

30ESK6, 30ESK6C,
30VSK6, 30VSK6C
4.92 3.12 2.75 3.437 4.00
125.0 79.25 69.85 87.3 101.6

40VSK6 6.00 3.12 2.18 3.50 3.96
152.4 79.25 55.4 88.9 100.6

* ± .02 [.05]
** For 30A & 40A ± .020 [.51]

 

Performance Data

Typical Insertion Loss
Measured in closed 50 ohm system

3 & 6VSK

10 & 20VSK

30VSK

40VSK

3 & 6 ESK

10 & 20 ESK

30ESK

 

Minimum Insertion Loss in dB:
Measured in closed 50 ohm system
     
Common Mode / Asymmetrical (Line to Ground)   Differential Mode / Symmetrical (Line to Line)

 
Current Rating Frequency - MHz
.01 .08 .1 .15 .5 1 5 10 30

VSK Models
3A, 6A, 10A 4 23 25 29 43 44 42 42 30
20A 7 23 25 29 43 44 48 48 48
30A 2 13 14 15 27 31 46 51 39
40A 2 15 18 22 40 43 45 50 30
ESK Models
3A, 6A, 10A 4 22 24 28 42 40 36 36 27
20A 7 22 24 28 35 38 45 45 45
30A 2 13 15 15 27 31 40 41 36

 
Current Rating Frequency - MHz
.01 .08 .1 .15 .5 1 5 10 30

VSK Models
3A, 6A 1 3 10 25 59 65 62 40 40
10A 1 3 3 10 55 65 65 50 50
20A 1 10 8 8 45 60 65 60 60
30A 5 13 13 13 60 60 51 43 43
40A 7 14 16 30 65 65 65 57 50
ESK Models
3A, 6A 1 3 10 25 59 65 62 40 40
10A 1 3 3 10 55 65 65 65 45
20A 1 10 8 8 45 60 65 60 60
30A 5 12 12 13 60 60 51 43 43

 

USA Customer Service: 1-800-468-2023
Corcom Products Direct: 1-847-680-7400
Germany: 49-89-6089-0
  Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.