| High Performance RFI Power Line Filters for Switching Power Supplies |
  
UL Recognized
CSA Certified
VDE Approved
Catalog Data Sheet
Printer friendly version |
|
 |
T Series
- Superior common-mode and premium
differential-mode attenuation
- Smaller package sizes than the EP Series
- Size and cost-effective
- ET models can help meet very low leakage
current requirements
Ordering Information

* IEC 60320-1 C14 inlet mates with C13 connector
Available Part Numbers
Click on any part number for 3D CAD models, customer drawings, distributor stock status and eCommerce Links.
Accessories
GA400: NEMA 5-15P to IEC 60320-1 C13 line cord

|
|
Specifications
| Maximum leakage current, each Line to Ground: |
| |
|
ET Models |
VT Models |
| |
@ 120 VAC 60 Hz
(3A, 6A, 10A) |
.30 mA |
.75 mA |
| |
@ 120 VAC 60 Hz
(15A, 20A) |
.30 mA |
1.2 mA |
| |
|
|
|
| |
@ 250 VAC 50 Hz
(3A, 6A, 10A) |
.50 mA |
1.2 mA |
| |
@ 250 VAC 50 Hz
(15A, 20A) |
.50 mA |
2.0 mA |
| |
|
|
| Hipot rating (one minute): |
| |
Line to Ground |
2250 VDC |
| |
Line to Line |
1450 VDC |
| |
|
|
| Operating Frequency: |
50 / 60 Hz |
| |
|
|
| Rated voltage (max.): |
250 VAC |
| |
|
|
| Rated Current: |
3A to 20A |
| |
|
| Operating Ambient Temperature Range (at rated current Ir): |
| |
|
-10°C to +40°C |
In an ambient temperature (Ta) higher than +40°C
the maximum operating current (Io) is calculated as
follows: Io = Ir √(85-Ta)/45
|
Electrical Schematics
3 & 6A

10A

15 & 20A

|
| Case Styles |
T1 (3, 6, 10A)

| Typical Dimensions: |
| |
Line/Load Terminals(4): |
.250 [6.3] with .07 [1.8] Dia. hole |
| |
Ground Terminal(1): |
.250 [6.3] with .07 x .16 [1.8 x 3.8] slot |
| |
Mounting Holes (2): |
.188 [4.75] Dia. |
T1 (15 & 20A)

| Typical Dimensions: |
| |
Line/Load Terminals(4): |
.250 [6.3] with .07 [1.8] Dia. hole |
| |
Ground Terminal(1): |
.250 [6.3] with .07 x .16 [1.8 x 3.8] slot |
| |
Mounting Slots (4): |
.250 x .156 [6.35 x 3.96] Dia. |
T3

| Typical Dimensions: |
|
| |
Wire leads (5): |
.4.0 [101.6] Min. AWG18 (AWG16 for 10A) |
| |
Mounting Holes (2): |
.188 [4.75] Dia. |
T6

| Typical Dimensions: |
|
| |
Terminals (5): |
8-32
Torque 18 lbf-in. [2.03 N-m] max. ±2[..22] |
| |
Mounting Slots (4): |
.250 x .156 [6.35 x 3.96] Dia. |
|
|
T7

| Typical Dimensions: |
| |
Load Terminals(2): |
.250 [6.3] with .07 [1.8] Dia. hole |
| |
Line Inlet (1): |
IEC-60320-1 C14 |
| |
Threaded Inserts (2): |
6-32 x 1/4 |
Recommended Panel Cutout

Tolerance ± .005 [0.13]
Back mount only
Case Dimensions
| Part No. |
A |
B |
C |
D |
E |
| (max.) |
(max.) |
(max.) |
± .015 |
(max.) |
| ± .38 |
| 3ET1, 6ET1 |
3.56 |
2.15 |
1.81 |
2.938 |
3.38 |
| 90.4 |
54.6 |
46.0 |
74.63 |
85.9 |
|
| 3ET3, 6ET3 |
2.55 |
2.15 |
1.81 |
2.938 |
3.38 |
| 64.8 |
54.6 |
46.0 |
74.63 |
85.9 |
|
| 3ET7, 6ET7 |
3.52 |
2.25 |
1.78 |
1.575 |
0.63* |
| 89.4 |
57.2 |
45.2 |
40.01 |
16.0* |
|
| 10ET1, 10VT1 |
4.69 |
2.27 |
1.80 |
4.063 |
4.47 |
| 119.1 |
57.7 |
45.7 |
103.2 |
113.5 |
|
| 10ET3, 10VT3 |
3.69 |
2.27 |
1.80 |
4.063 |
4.47 |
| 93.7 |
57.7 |
45.7 |
103.2 |
113.5 |
|
15ET1, 15VT1,
20ET1, 20VT1 |
5.45 |
3.12 |
2.18 |
3.50 |
3.96 |
| 138.4 |
79.2 |
55.4 |
88.9 |
100.6 |
|
15ET6, 15VT6,
20ET6, 20VT6 |
5.95 |
3.12 |
2.18 |
3.50 |
3.96 |
| 151.1 |
79.2 |
55.4 |
88.9 |
100.6 |
|
| * ± .02 [.5] |
|
Performance Data
| Typical Insertion Loss |
| Measured in closed 50 ohm system |
| |
3ET

|
6ET

|
10ET

|
15ET

|
20ET

|
10VT

|
15VT

|
20VT

|
 |
| Minimum Insertion Loss in dB: |
| Measured in closed 50 ohm system |
| |
|
|
| Common Mode / Asymmetrical (Line to Ground) |
|
Differential Mode / Symmetrical (Line to Line) |
|
|
|
| Current Rating |
Frequency - MHz |
| .01 |
.03 |
.05 |
.15 |
.5 |
1 |
2 |
5 |
10 |
20 |
30 |
|
| ET Models |
| 3A |
22 |
32 |
36 |
46 |
47 |
44 |
43 |
40 |
42 |
42 |
42 |
| 6A |
16 |
26 |
30 |
41 |
47 |
44 |
43 |
43 |
40 |
42 |
42 |
| 10A |
12 |
22 |
26 |
36 |
47 |
42 |
42 |
40 |
42 |
42 |
45 |
| 15A |
8 |
17 |
22 |
31 |
43 |
44 |
44 |
42 |
47 |
52 |
43 |
| 20A |
3 |
12 |
17 |
26 |
34 |
36 |
37 |
37 |
42 |
47 |
38 |
| VT Models |
| 10A |
12 |
22 |
26 |
38 |
52 |
50 |
50 |
50 |
50 |
50 |
50 |
| 15A |
8 |
17 |
22 |
33 |
52 |
52 |
52 |
52 |
57 |
45 |
35 |
| 20A |
3 |
12 |
17 |
29 |
42 |
47 |
50 |
51 |
55 |
40 |
30 |
|
|
|
| Current Rating |
Frequency - MHz |
| .01 |
.03 |
.05 |
.15 |
.5 |
1 |
2 |
5 |
10 |
20 |
30 |
|
| ET Models |
| 3A |
3 |
1 |
30 |
61 |
70 |
70 |
70 |
50 |
50 |
50 |
55 |
| 6A |
4 |
2 |
14 |
51 |
70 |
70 |
70 |
65 |
47 |
50 |
55 |
| 10A |
7 |
12 |
17 |
52 |
70 |
70 |
70 |
65 |
55 |
50 |
60 |
| 15A |
12 |
19 |
15 |
51 |
70 |
70 |
70 |
70 |
70 |
65 |
60 |
| 20A |
10 |
17 |
13 |
51 |
70 |
70 |
70 |
70 |
67 |
65 |
60 |
| VT Models |
| 10A |
7 |
12 |
17 |
52 |
70 |
70 |
70 |
65 |
65 |
50 |
65 |
| 15A |
12 |
19 |
15 |
51 |
70 |
70 |
70 |
70 |
70 |
65 |
60 |
| 20A |
10 |
17 |
13 |
51 |
70 |
70 |
70 |
70 |
67 |
65 |
60 |
|
|
|
| USA Customer Service: |
1-800-468-2023 |
| Corcom Products Direct: |
1-847-680-7400 |
| Germany: |
49-89-6089-0 |
|
|
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. |